Flexible Heavy Duty Cables
 
 
 

Product applications

Cardiff flexible heavy duty cables are mainly used for extension leads or lights appliance leads heavy duty PVC flexible cables. The cables are manufactured based on AS 3191.

Constructions

Conductor: fine strands of bare copper, acc. To DIN VED 0295 class 5 resp. IEC 60228 cl.5

insulation: heavy duty PVC type V75

insulation colour: Brown,blue, Green/Yellow

sheath: heavy duty PVC type V75

Technical data:

Rated voltage: 0.6/1kv

Conductor operating temperature: -25°C-75°C

Short circuit temperature 160°C

Bending radius: Flexible applicantion: 4x cable O.D.

                                Fixed installation: 6x cable O.D.

Maximum pulling tension: 20N/mm2 x total cross-sectional area of phase conductor   

Part number

Nominal CSA mm2

Conductor strands mm

Core diamenter

mm

Cable diameter mm

Cable weight kg/100m

Max d.c resistanceΩ/km

Current rating

A

1315

1.5

30/0.25

3.01

10.05

14.50

13.3

16

 

 

 

 

Standards:

AS/NZS 3191   AS/NZS 3808

AS/NZS 1125   IEC 60228

 
 