TÜV PV1-F Fig8 511

Product Category:Solar Cable

Product Description:TV PV1-F Fig8 511 Acc. to TV 2PfG 1169 certification. Construction: Conductor: Fine strands of tinned copper, acc. to IEC 60228 cl.5 Insulation: XLPO Insulation colour: Red (+) Black (-) Outer sheath: XLPO Sheath colour: Black, RAL 9005 Tec

Detailed
TÜV PV1-F Fig8 511


Acc. to TÜV 2PfG 1169 certification.

 

 
Construction:
Conductor: Fine strands of tinned copper, acc. to IEC 60228 cl.5
Insulation: XLPO
Insulation colour: Red (+) & Black (-)
Outer sheath: XLPO
Sheath colour: Black, RAL 9005
 
Technical data:
Rated voltage : 1000V AC, 1500V DC
Test voltage  : 6500V
Ambient Temp.: -40℃ to +90℃ (Max. Temp. at conductor: 120℃)
Bending radius : D<8mm: 4x cable diameter
D≥8mm: 6x cable diameter
Weathering & UV-resistance: HD 605/A1
Cold bending test : EN 60811-1-4
Burning behavior  : IEC 60332-1-2
O-zone resistance : EN 50396
Resistance against & Alkaline solution: EN 60811-2-1
 
 
 
 
Part No. Cores No. + area (mm²) Conductor structure (core/mm)  Conductor Diameter (mm) Approx. Diameter (mm) Max conductor DC resistance (20℃; Ω/KM) Approx. Weight (kg/km) Reference current (60℃; A) 
511 00150 011 1.5 30/0.25 1.58 3.8X7.8 13.700 35.9 30
511 00250 011 2.5 47/0.25 1.98 4.2X8.6 8.210 46.5 41
511 00400 011 4.0 52/0.30 2.50 4.6X9.4 5.090 62.8 55
511 00600 011 6.0 78/0.30 3.06 5.3X10.8 3.390 86.6 70
511 01000 011 10 80/0.40 4.56 7.0X14.2 1.950 153.2 98
511 01600 011 16 128/0.40 5.60 10.0X20.4 1.240 216.7 132
511 02500 011 25 192/0.40 6.95 11.8X24.0 0.795 328.6 176
511 03500 011 35 276/0.40 8.74 13.2X26.8 0.565 449.9 218